In this blog post, we’ll examine the structure of the Sampoong Department Store and the process of its collapse, exploring how shoddy design and construction, along with reckless changes in building use, led to this massive disaster.
Introduction
On June 29, 1995, the north wing of the Sampoong Department Store in Seocho-gu, Seoul—which housed a dense concentration of stores—collapsed. It wasn’t caused by an earthquake or a bomb explosion. A major section of the five-story building—where people had been coming and going just moments before—collapsed in about 20 seconds. What on earth was happening inside the building, which appeared to be standing upright from the outside?
To solve this mystery, we must first understand how a building supports its own weight. The collapse of Sampoong Department Store cannot be fully explained by simply attributing it to a single weak column. With the connection points where the floor slabs and columns exchanged forces already weakened, the weight the building had to bear actually increased. As the failure at those connection points spread to surrounding areas, it compromised the safety of the entire building.
A structure where columns directly support floor slabs
The Sampoong Department Store was built using a flat-slab structure, in which columns directly support the floor slabs without beams. The “flat slab” mentioned in the manuscript refers to this type of structure. A slab is a reinforced concrete panel that serves as the floor of one level and the ceiling of the level directly below. Beams are members that span the distance between columns to support the slab; however, in a flat-slab structure, the weight of the slab is transferred directly to the columns without passing through the beams.
It is easier to understand if you picture some underground parking garages. Columns are spaced at regular intervals across a large open space, and the ceiling between the columns extends in a flat, continuous surface. This type of structure is ideal for utilizing space in a spacious and flexible manner. However, since the weight borne by the large floor area is concentrated around the relatively narrow columns, the points where the slab meets the columns must be made sufficiently strong.
The key point here is that it is not enough for just the columns to be strong. Even if the columns remain standing, the floor slab may sag if the surrounding slab cannot withstand the load. The phenomenon where the slab is punctured and fails along the perimeter of the columns is called “punching shear failure.” Imagine pressing down on a thin plate supported at one end by a rod; the plate will sag as the area around the rod tears. In actual buildings, concrete and rebar work together to resist loads, but if the force exceeds what the connection points can withstand, a similar form of failure occurs.
One way to prevent this is through the use of a “column base.” Rather than a separate plate inserted onto top of the column, a column base refers to a section of the slab surrounding the column that is made thicker than the surrounding areas. You can see this reinforcement method in parking garage ceilings, where the slab around the top of a column is wider and thicker than the surrounding area. The key is to properly determine the column size, slab thickness, and the amount and placement of rebar so that the connection can withstand sufficient force.
They reduced the load-bearing capacity while increasing the weight to be supported
At the Sampoong Department Store, these structural requirements were not properly followed. According to a 2002 study by Gardner, Heo Jeong-seok, and Jeong Ran, which analyzed the collapse investigation report, the diameter of some columns supporting the upper floors was 60 cm—smaller than the 80 cm assumed in the structural calculations. There were also problems with the placement of rebar in the slabs, and the required base plates were not installed around some columns. In other words, the structural joints designed to bear the load did not possess the resistance expected in the calculations.
However, the weight placed on the building increased even further. The fifth floor was originally planned as a roller-skating rink but was converted into a restaurant area. Although walls and flooring were added during the renovation to accommodate the restaurants, the structure was not reinforced accordingly. The same study analyzed that this change of use caused the dead load on the fifth floor to increase by approximately 35 percent.
Dead load refers to the weight continuously borne by a building—such as floor finishes and walls—rather than the weight of people or movable objects, which fluctuates frequently.
The roof also bore an increasing burden. The load from the weight of the cooling tower used for air conditioning was approximately 4 kPa, which was four times the 1 kPa roof live load considered in the structural calculations. Here, kPa is a unit representing the force acting per unit area. This comparison means that the load from the cooling tower was significantly greater than the roof load considered in the design; it does not mean it was four times the total load the entire roof could withstand. The investigation also pointed out that the roof slab was damaged during the process of moving the cooling tower.
These issues were not isolated from one another. While the forces the building had to withstand increased, the capacity of the structural connections to transfer those forces decreased. If one attempts to explain the collapse by focusing on a single defect in isolation, one misses the process by which multiple errors compounded to exhaust the safety margin.
The Failure of a Single Joint Triggers a Chain Reaction of Collapse
The building showed signs of trouble before it collapsed. Photographs of the rooftop and the food court taken before the collapse show cracks and bulges on the surface, as well as signs of the ceiling finish coming apart. While these photographs alone cannot confirm the extent of internal structural damage or the exact sequence of the collapse, the cracks and sagging reported prior to the accident were signs that should have raised doubts about the building’s safety. The National Archives of Korea also cites management’s complacent response to signs of collapse as a key factor contributing to the high number of casualties.
It is necessary to clarify the exact location of the initial failure point. The investigation committee determined that the collapse began at the junction of a specific column and floor slab in the fifth-floor food court. A subsequent study reviewing this finding suggested the possibility that the failure may have started at the connection between the same column and the rooftop slab. Therefore, rather than concluding that the rooftop floor slab fell first and crashed onto the fifth floor, it is more accurate to explain that the failure of the column-to-slab joints on the upper floors led to a chain reaction of collapse.
When one joint fails, the weight it was supporting is transferred to the surrounding joints. If the surrounding areas cannot withstand this additional load, the failure spreads to a wider area. Furthermore, if floor slabs from upper floors fall onto lower floors, the lower floors must bear not only the increased weight but also the impact of the fall. This phenomenon, in which localized damage spreads to a large portion of the building, is called “progressive collapse.”
At the Sampoong Department Store, this chain reaction caused floor slabs from multiple stories to collapse, and debris piled up all the way to the basement. Photographs taken after the collapse show that while some structural elements on either side remained standing, the store areas that had filled the space between them had vanished. The appearance of the building having sunk entirely into the ground was the result of the floor slabs losing their load-bearing capacity and collapsing in a stacked manner.
Safety is not guaranteed by the name of a construction method alone
It would be incorrect to attribute the collapse of the Sampoong Department Store solely to a flaw in the flat-slab structure itself. A flat-slab structure is a viable construction method provided that the required loads are accurately calculated and the connections are properly designed and constructed. At the same time, given its characteristic lack of beams, measures must be in place to prevent punching shear failure and cascading collapse. Safety is not a guarantee attached to the name of a construction method; it is the result of adhering to the conditions of design, construction, inspection, and maintenance.
The fact that a building stood for several years without collapsing is not proof of safety. A building can withstand defects for a certain period of time. However, if its use changes or heavy equipment is added, even the remaining safety margin may disappear. When cracks and sagging appear, what is needed is not the expectation that “since it has held up so far, it will be fine going forward,” but rather a judgment to identify the risk and protect people.
Although the Sampoong Department Store collapsed in a short period of time, the conditions leading to the collapse were created over a long period. A series of factors accumulated: construction that deviated from the design, modifications that did not adequately account for loads, and decisions that failed to respond appropriately even after warning signs were observed. No matter how advanced architectural technology may be, it cannot compensate for human judgment that ignores the conditions required by that technology.